GBT — Glover Backflow Testing logo Glover Backflow TestingProudly serving North Central Texas

Reference

Backflow Prevention Devices and Assemblies

RPZ, double check, PVB, SVB, AVB and air gap — how each one works, what it protects against, where Texas rules require it, and what we test.

Two words matter on this page. Hazard: Texas classifies every cross-connection as a health hazard (could make someone sick — chemicals, sewage, medical, process water) or a non-health hazard (unpleasant but not toxic — stagnant water, heat, color, taste). Direction: a device is rated for backsiphonage only, or for backsiphonage and backpressure. The device you need is set by both. See what backflow testing is for the plain-English background.

Reduced Pressure Zone Assembly (RPZ, RP, RPBA, RPPA)

Health hazardBacksiphonage + backpressureTestable assembly
  • Protects againstBacksiphonage and backpressure, high (health) hazard
  • PartsTwo independent spring-loaded check valves, a hydraulically operated relief valve between them, two shutoffs, four test cocks
  • Where requiredAny health-hazard connection: medical/dental/vet, restaurants with chemical feed, car washes, labs, manufacturing, irrigation with fertilizer injection, private wells on city water, boilers with chemical treatment, fire lines with antifreeze or foam
  • InstallationHorizontal (most models), minimum 12 in. above grade or flood level, never in a pit or vault that can flood, needs a drain that can take full relief-valve discharge, protected from freezing
  • Test criteria (USC)Check #1 holds ≥ 5.0 psid; check #2 holds ≥ 1.0 psid; relief valve opens at ≥ 2.0 psid

The RPZ is the highest level of mechanical protection. Between its two checks is the zone of reduced pressure: a chamber deliberately held a few psi below supply pressure. If either check leaks, or pressure reverses, the relief valve opens and dumps water out of the zone to atmosphere — so the contaminated water goes on the ground, not into the main. That discharge is a feature, not a defect, but it is also why an RPZ can never go where the discharge could flood something.

Because it is spring-loaded and held under a pressure differential, an RPZ costs a few psi of pressure and, on a large domestic service, that matters for sizing. It also dribbles briefly during normal pressure fluctuations; a steady stream from the relief port means a fouled first check or a failed relief valve and it needs service.

Reduced pressure principle assembly schematicShutoff #1Shutoff #2#1check 1#2check 2TC1TC2TC3TC4Relief valve discharge (to air gap / drain)ZONE OF REDUCED PRESSUREFLOW
Schematic. Water enters left; the relief valve under the zone discharges to atmosphere whenever zone pressure gets within 2 psid of supply.

Double Check Valve Assembly (DCVA, DC, DCA)

Non-health hazard onlyBacksiphonage + backpressureTestable assembly
  • Protects againstBacksiphonage and backpressure, non-health (pollutant) hazard only
  • PartsTwo independent spring-loaded check valves in series, two shutoffs, four test cocks; no relief valve
  • Where requiredIrrigation without chemical injection (most common residential/commercial DC), fire sprinkler systems without additives (as a DCDA), domestic heating systems, degreasers, buildings with large elevation differences, general commercial service isolation where no health hazard exists
  • InstallationHorizontal or vertical per model listing, may be installed below grade in a vault or box (no discharge), keep accessible for testing, protect from freezing
  • Test criteria (USC)Each check holds tight in reverse and closes at ≥ 1.0 psid

Two checks in series: if one sticks or leaks, the second still holds. That redundancy is why it is accepted for backpressure. What it lacks is any way to tell you it has failed — there is no relief valve, no discharge, no visual sign. A double check with both checks fouled looks exactly like a good one. That is the entire argument for the annual test, and it is why Texas will not accept a DC on a health hazard.

Most in-ground irrigation systems in North Texas have a DC in a green valve box near the meter. Common failure: debris on a check seat after a main repair or a new installation flushes grit through it.

Double check valve assembly schematicShutoff #1Shutoff #2#1check 1#2check 2TC1TC2TC3TC4FLOW
Schematic. Two checks, four test cocks, two shutoffs. Nothing discharges — only a gauge can tell you whether it still holds.

Pressure Vacuum Breaker (PVB)

Health or non-health hazard*Backsiphonage ONLYTestable assembly
  • Protects againstBacksiphonage only. Cannot stop backpressure — no pumps, boilers or elevated tanks downstream
  • PartsOne spring-loaded check valve, one spring-loaded air inlet valve above it, two shutoffs, two test cocks
  • Where requiredIrrigation systems (the most common residential unit in Texas), hose bib manifolds, non-pressurized process outlets. *Approved for health hazards only where the only possible backflow mechanism is backsiphonage
  • InstallationVertical, at least 12 in. above the highest downstream outlet or sprinkler head, outdoors or where the air-inlet discharge can spill harmlessly; will freeze if not protected
  • Test criteria (USC)Air inlet opens at ≥ 1.0 psid; check valve holds at ≥ 1.0 psid

The PVB works on a simple idea: if supply pressure ever drops, a spring pops the air inlet open and lets air into the line, which breaks the siphon before water can be pulled backward. Under normal pressure the air inlet is held shut and the check keeps the line closed. Because it lets air in it also lets a little water out when it operates, so it goes outdoors. The 12-inch height rule exists so no sprinkler head can sit higher than the air inlet and back-siphon through it.

The PVB is the unit you see on a riser next to a house with a sprinkler system. It is compact, cheap and easy to rebuild, and it is also the assembly most often destroyed by a hard freeze because it sits above ground full of water. If your irrigation system injects fertilizer, a PVB is no longer enough — Texas rules move that connection to an RPZ.

Pressure vacuum breaker schematicair enters when supply pressure dropsAir inlet valveSpring-loaded checkTC2TC1Shutoff #1Shutoff #2FROM SUPPLYTO SYSTEM12 in. min. above highest downstream outlet
Schematic. Under loss of supply pressure the air inlet at the top opens and the siphon is broken. It offers no protection against pressure pushing back from downstream.

Spill-Resistant Vacuum Breaker (SVB, SRVB)

Health or non-health hazard*Backsiphonage ONLYTestable assembly
  • Protects againstBacksiphonage only, same limits as a PVB
  • PartsOne check, one air inlet with a bleed/vent arrangement that keeps it from spitting water on start-up, two shutoffs, one test cock plus a vent port
  • Where requiredSame applications as a PVB but indoors or anywhere spillage from a standard PVB would be a problem — labs, commercial kitchens, mechanical rooms
  • InstallationVertical, 12 in. above the highest downstream outlet, accessible for testing
  • Test criteria (USC)Air inlet opens at ≥ 1.0 psid; check holds at ≥ 1.0 psid

A PVB spits a little water every time the line pressurizes and the air inlet snaps shut. Indoors that is a nuisance and sometimes a real problem. The SVB adds an internal design that seals the air inlet before the check opens, so it does the same job without the spill. Functionally it is a PVB for indoor use and it is tested the same way.

Pressure vacuum breaker schematicair enters when supply pressure dropsAir inlet valveSpring-loaded checkTC2TC1Shutoff #1Shutoff #2FROM SUPPLYTO SYSTEM12 in. min. above highest downstream outlet
Same principle as the PVB — check valve below, air inlet above — with an internal arrangement that keeps it from spilling on pressurization.

Atmospheric Vacuum Breaker (AVB)

Low hazard onlyBacksiphonage ONLYDevice, not testable
  • Protects againstBacksiphonage only
  • PartsA single float or poppet that drops open to atmosphere when flow stops; no springs, no test cocks
  • Where requiredHose bibs, shampoo sinks, laboratory faucets, some commercial kitchen equipment, older irrigation zone valves (one AVB per zone, downstream of the valve). Listed as acceptable for those items in 30 TAC 290.47(f)
  • Installation6 in. above the highest downstream outlet, NO shutoff valve downstream of it, must not be under continuous pressure for more than 12 hours — it only works when the water is off
  • Test criteriaNone. An AVB cannot be field tested; it is inspected visually

The simplest device: while water flows, it lifts a float that seals the vent; when flow stops, the float drops and the vent opens to air, so there is no way to siphon through it. The catch is that it only works with the water off and nothing closed downstream. Put a shutoff valve after it and hold it under pressure, and the float stays seated, the poppet can stick, and the protection is gone. That is why it is a device, not an assembly, and why cities push irrigation systems toward a PVB or DC at the point of connection instead.

Atmospheric vacuum breaker schematicFloat / poppetvent open to air whenever flow stopsShutoff (upstream only)FROM SUPPLYTO OUTLETNo shutoff valve downstreamNot under continuous pressure > 12 hours6 in. above the highest outlet
Schematic. With flow stopped the float drops and the vent opens. It cannot have a valve downstream and cannot be tested with a gauge.

Air Gap (AG)

Highest protectionAll hazards, both directionsNothing to test
  • Protects againstEverything — there is no pipe for water to flow back through
  • PartsNone. A physical, unobstructed vertical separation between the supply outlet and the flood-level rim of whatever it feeds
  • Where requiredSewage lift stations and ejectors, chemical-additive cooling towers, trap primers, bulk water fill stations (30 TAC 290.44(h)(3)), tank fills, anywhere an RPZ is unacceptable
  • InstallationGap of at least twice the supply pipe diameter and never less than 1 in.; the outlet must not be able to be submerged, and the gap cannot be defeated by a hose
  • Test criteriaVisual inspection: is the gap still there and still the right size?

Water falls through open air into a tank, sink or drain. Nothing mechanical means nothing to wear out, freeze or foul, which is why it is the required protection for the worst hazards. Its costs are pressure (you lose all of it — the tank side needs its own pump) and space. In practice an air gap is designed into the equipment; we verify it during a hazard survey rather than “testing” it.

Air gap schematicReceiving tank / sink(flood-level rim)Air gap = 2× pipe diameter (min. 1 in.)Nothing to test, nothing to fail.Open air between the supply outletand the highest possible water level.Required for sewage, chemical-additivecooling towers and trap primers(30 TAC 290.47(f)).FLOW
The gap between the pipe outlet and the highest possible water level is the protection. Twice the pipe diameter, minimum one inch.

Fire line detector assemblies (DCDA, RPDA)

Fire sprinkler serviceApproved fireline contractor required

A fire sprinkler system is a cross-connection: a large volume of water that sits in black-steel pipe for years, sometimes with antifreeze or foam. The assembly on a fire service is a full-size double check or RPZ with a small bypass line carrying a water meter and its own small check valve. The bypass meter “detects” low flow — a leak or unauthorized use — without the pressure loss of metering the whole fire main. A system with plain water gets a DCDA; one with antifreeze, foam or a non-potable auxiliary supply gets an RPDA.

Texas requires the tester on a fire line to be employed by a TCEQ-approved fireline contractor. TCEQ regulatory guidance RG-345 covers the specifics. We are happy to test the domestic and irrigation assemblies at a commercial property and coordinate the fire line test with your sprinkler contractor.

Ductile iron double check valve assembly with two OS&Y gate valves
A full-size iron DC with OS&Y gate valves, the body used on most fire service DCDAs.

Which one does my property need?

Texas answers this in a table — 30 TAC §290.47(f), Assessment of Hazards and Selection of Assemblies. The rows people actually ask about:

Connection or premisesHazardMinimum assembly
Irrigation system, no chemical injectionNon-healthDCVA, PVB or AVB (per zone)
Irrigation system with chemical / fertilizer injectionHealthRPZ
Hose bibNon-healthAVB (hose-bib vacuum breaker)
Private swimming pool fillNon-healthPVB or air gap
Public swimming poolNon-healthRPZ or air gap
Domestic heating boiler / space heatingNon-healthDCVA (RPZ if chemically treated)
Commercial kitchen equipment, shampoo basinsNon-healthAVB
Beverage carbonators, vending machinesNon-healthRPZ or PVB (stainless/RP per local code)
Medical, dental, veterinary, laboratory, mortuaryHealthRPZ at the service (AVB/PVB on individual fixtures)
Restaurants, car washes, laundries, food processingHealthRPZ or air gap
Sewer connections, sewage ejectors, trap primersHealthAir gap
Cooling tower with chemical additivesHealthAir gap
Private well or rainwater system on a premises with public waterHealthRPZ or air gap
Hospitals, chemical/plating plants, petroleum, marinas, docksHealthRPZ or air gap
Fire sprinkler system, plain waterNon-healthDCDA
Fire sprinkler system with antifreeze/foam or auxiliary supplyHealthRPDA

Condensed from Figure: 30 TAC §290.47(f). The full table is in the Texas laws page. Your city may require more than the state minimum — several North Texas cities require a DC or PVB rather than an AVB on all new irrigation systems, and some require an RPZ on any commercial service.

Brands and models we see

Most assemblies in North Texas are made by Watts, Febco, Zurn Wilkins, Apollo (Conbraco) and Ames. Typical residential irrigation units: Febco 765 and Wilkins 720A (PVB); Watts 007/LF007, Febco 850 and Wilkins 950XL (DC). Typical health-hazard units: Watts 009/LF009 and 909, Febco 825Y, Wilkins 975XL and 375 (RPZ). Any assembly on a required connection in Texas has to be listed by USC FCCCHR (or another TCEQ-recognized approval), and the make, model, size and serial number go on every test report. If you do not know what you have, text us a photo of the tag.

Every assembly type above except the AVB and the air gap is a testable assembly — two shutoffs, test cocks, and a USC procedure — and every testable assembly on a required connection in Texas is tested at installation and every 12 months. That is what we do.

Need a backflow test or repair?

Call or text and talk to the tester, not a call center. Same-week scheduling across Dallas–Fort Worth, Denton, Decatur, Gainesville and Wichita Falls.

(940) 351-6040

Request a test online